| Suntube
IV Clearances to Combustibles |
|
MBTUH
INPUT NAT OR LP
|
40
|
45,50
|
55,60
|
65,70
75,80
85
|
|
100
|
105,110
115,120
125
|
130,135
140,145
|
150
|
155,160
165,170
175
|
180,185
190,195
200
|
|
|
AVAILABLE
TUBE LENGTH (FEET)
|
10,15
20
|
20'
|
20'
|
20'
25' §
|
30',35'§
40'
|
30',35'§
40' 45'§
50'
|
40'
45'§
50'
|
40'
45'§
50'
|
40'
45'§
50' 55'§
60', 65'§
70'
|
50'
55'§
60', 65'§
70'
|
50'
55'§
60', 65'§
70'
|
|
CLEARANCES*
(INCHES)
TOP OF REFLECTOR
|
12
|
12
|
12
|
12
|
12
|
12
|
12
|
12
|
12
|
12
|
12
|
|
|
|
FRONT
OF REFLECTOR
MOUNTED 0
|
40
|
40
|
50
|
24"
|
24"
|
24"
|
32"
|
48"
|
48"
|
58"
|
68"
|
|
MOUNTED 1 to 30
|
40
|
40
|
50
|
24"
|
24"
|
24"
|
32"
|
48"
|
48"
|
58"
|
68"
|
|
MOUNTED 31 to 45
|
40
|
40
|
50
|
x
|
x
|
x
|
x
|
70"
|
70"
|
80"
|
90"
|
|
|
|
REAR OF REFLECTOR
MOUNTED 0
|
40
|
40
|
50
|
24"
|
24"
|
24"
|
32"
|
48"
|
48"
|
58"
|
68"
|
|
MOUNTED 1 to 30
|
40
|
40
|
50
|
24"
|
24"
|
24"
|
32"
|
48"
|
48"
|
58"
|
68"
|
|
MOUNTED 31 to 45
|
12
|
12
|
12
|
x
|
x
|
x
|
x
|
12
|
12
|
12
|
12
|
| |
|
BELOW REFLECTOR
|
40
|
40
|
50
|
60
|
60
|
60
|
72
|
82
|
82
|
92
|
92
|
|
|
Natural gas Only § Not Available
in U-Tube configuration * For all
systems: 12" from burner end and 68" from U-Bend
|
|
|
System
Information
Manifold Operating Pressure
Natural Gas
& LP/Propane: 3.5" WC
Minimum Inlet Pressure
Natural Gas:
40-125 MBTUH 6" WC
130-200 MBTUH 7"WC
LP/Propane:
All MBTUH 11" WC
1/2"FPT Gas Inlet
Electrical Rating:
120 VAC-60
Hz-1 Phase
|
|
|
Solaronics
U-Tube heaters maintain employee comfort in NJ plant.
Ask for Case History 62. |
|
|
| Warranty
: 10 year limited warranty on All combustion and heat exchanger
tubes, 10 year limited warranty on Burner Core, 2 year limited warranty
on All Burner Controls |
|

Leader in Quality Gas-Fired Infra-Red Products
Solaronics, Inc. P.O. Box 80217 704 Woodward Ave.
Rochester, MI 48308-0217
Phone: (800) 223-5335 Phone: (248) 651-5333 Fax:
(248) 651-0357
|
|